2 | General safety precautions
Installer reference guide
14
RZASG100~140MUV/Y
Sky Air Advance-series
4P743506-1 – 2023.08
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
Install power cables at least 1 meter away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 meter may NOT be
sufficient.
NOTICE
ONLY applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes ON and OFF while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.