3 | Specific installer safety instructions
Installer reference guide
17
RZASG100~140MUV/Y
Sky Air Advance-series
4P743506-1B – 2024.05
WARNING
▪ If the power supply has a missing or wrong N-phase, equipment might break
down.
▪ Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shocks.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, extension cords, or connections from a star system.
They can cause overheating, electrical shocks or fire.
▪ Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
CAUTION
Do NOT push or place redundant cable length into the unit.
CAUTION
For use of units in applications with temperature alarm settings it is recommended to
foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature
is exceeded. The unit may stop for several minutes during normal operation for
"defrosting the unit", or when in "thermostat stop" operation.
WARNING
Do NOT interchange the supply conductors L and the neutral conductor N.
Charging refrigerant (see
"9Charging refrigerant"[
4
56]
)
WARNING
Charging of refrigerant MUST be in accordance with the instructions from this
manual. See "9Charging refrigerant"[456].
WARNING
Some sections of the refrigerant circuit may be isolated from other sections caused
by components with specific functions (e.g. valves). The refrigerant circuit therefore
features additional service ports for vacuuming, pressure relief or pressurizing the
circuit.
In case it is required to perform brazing on the unit, ensure that there is no pressure
remaining inside the unit. Internal pressures need to be released with ALL the service
ports indicated on the figures below opened. The location is depending on model
type.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.