Daikin RZAG125N2V1B handleiding
Handleiding
Je bekijkt pagina 67 van 88

8 | Commissioning
Installer reference guide
67
RZAG71~140N
Sky Air Alpha-series
4P695307-1A – 2024.02
# Action
1 Open the liquid stop valve and gas stop valve by removing the cap
and turning counterclockwise with a hex wrench until it stops.
2 Close the service cover to prevent electric shocks.
3 Turn ON power for at least 6hours before starting operation to
protect the compressor.
4 On the user interface, set the unit to cooling operation mode.
2 Start the test run
# Action Result
1 Go to the home menu.
Cool
Set to
28°C
2 Press at least 4seconds. The Service Settings menu is
displayed.
3 Select Test Operation.
Return Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
4 Press. Test Operation is displayed on
the home menu.
Cool
Return Setting
Test Operation
5 Press within 10seconds. Test run starts.
3 Check operation for 3minutes.
4 Check operation of the airflow direction (only applicable for indoor units with
swing flaps).
# Action Result
1 Press.
Return Setting
Return Setting
Air Volume/direction
Air Volume Direction
Position 0
Low
2 Select Position 0.
Return Setting
Return Setting
Air Volume/direction
Air Volume Direction
Low
Position 0
3 Change the position. If the airflow flap of the indoor
unit moves, operation is OK.
If not, operation is not OK.
Bekijk gratis de handleiding van Daikin RZAG125N2V1B, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Daikin |
| Model | RZAG125N2V1B |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 11803 MB |







