7 | Installation
Installer reference guide
44
RZAG71~140N
Sky Air Alpha-series
4P695307-1A – 2024.02
7.4.8 To connect the refrigerant piping to the outdoor unit
Piping length. Keep field piping as short as possible.
Piping protection. Protect the field piping against physical damage.
1 Do the following:
Remove the service cover (a) with screw (b).
Remove the piping intake plate (c) with screws (d).
a
c
b
d d
2 Choose a piping route (a, b, c or d).
a
d
b
c
a Front
b Side
c Rear
d Bottom
INFORMATION
b b bb
a
a
Remove the knockout hole (a) in the bottom plate or cover plate by tapping on
the attachment points with a flat head screwdriver and a hammer.
Optionally, cut out the slits (b) with a metal saw.