6 | Preparation
Installer reference guide
32
RZAG71~140N
Sky Air Alpha-series
4P695307-1A – 2024.02
Requirement Limit
71 100 125+140
3 Maximum allowable piping length Pair: N/A
Twin: L1+L2+L3≤Limit 65m 85m
Triple: L1+L2+L3+L4≤Limit 85m
Double twin:
L1+L2+L3+L4+L5+L6+L7≤Limit
85m
4 Maximum branch piping length Pair: N/A 10m
Twin and triple: L2≤Limit
Double twin: L2+L4≤Limit
20m
5 Maximum difference between
branch lengths
Pair: N/A
Twin: L2–L3≤Limit 10m
Triple: L2–L4≤Limit 10m
Double twin:
L2–L3≤Limit
L4–L5≤Limit
L6–L7≤Limit
(L2+L4)–(L3+L7)≤Limit
10m
6 Maximum height between indoor
and outdoor
Pair, twin, triple and double twin:
H1≤Limit
30m
7 Maximum height between
indoors
Pair: N/A
Twin, triple and double twin:
H2≤Limit
0.5m
(a)
Parenthesised figure represents the equivalent length.
Example
If the system layout is as follows… Then the requirements are…
RZAG125
Triple:
L2
L3
L4
H1
H2
L1
Østandard
1 3m≤L1+L4
2 L1+L2≤85m (100m)
3 L1+L2+L3+L4≤85m
4 L2≤20m
5 L2–L4≤10m
6 H1≤30m
7 H2≤0.5m
6.3.2 Refrigerant piping insulation
Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness