Daikin RYYQ24U7Y1B handleiding

48 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 30 van 48
15 Electrical installation
Installation and operation manual
30
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546220-1F – 2023.01
a
b
dd d
c
b g g
h h
c
fffh
eee
a
h h h
h h
i
a Field power supply (with earth leakage protector)
b Main switch
c Earth connection
d Outdoor unit
e Indoor unit
f User interface
g Indoor power supply wiring (sheathed cable) (230V)
h Transmission wiring (sheathed cable) (16V)
i Outdoor power supply wiring (sheathed cable)
Power supply 3N~50Hz
Power supply 1~50Hz
Earth wiring
15.4 To route and fix the transmission
wiring
Transmission wiring can be routed through the front side only. Fix it
to the upper mounting hole.
b a
A
b a
c
c
c
d
c
d
c
8~12 HP 14~20 HP
A
A
a Transmission wiring (possibility 1)
(a)
b Transmission wiring (possibility 2)
(a)
. Fix to pipe insulation
with tie wraps.
c Tie wrap. Fix to factory-mounted low voltage wiring.
d Tie wrap.
(a) Knockout hole has to be removed. Close the hole to avoid
small animals or dirt from entering.
X1A
c
d
a b a b
8~12 HP 14~20 HP
Fix to the indicated plastic brackets using field supplied clamping
material.
a Wiring between the units (indoor-outdoor) (F1/F2 left)
b Internal transmission wiring (Q1/Q2)
c Plastic bracket
d Field supplied clamps
15.5 To connect the transmission wiring
The wiring from the indoor units must be connected to the F1/F2
(In‑Out) terminals on the PCB in the outdoor unit.
Tightening torque for the transmission wiring terminal screws:
Screw size Tightening torque (N•m)
M3.5 (A1P) 0.8~0.96
In case of single outdoor unit installation
F1 F2 F1 F2 Q1 Q2
F1 F1F2 F2 Q1 Q2
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
b
c
a
d
e
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
A1P
a Outdoor unit PCB (A1P)
b Use the conductor of sheathed wire (2 wire) (no polarity)
c Terminal board (field supply)
d Indoor unit
e Outdoor unit
In case of multi outdoor unit installation
F1 F2 F1 F2 Q1 Q2 Q1 Q2
A1P
d de
f
ba c
Q1 Q2
a Unit A (master outdoor unit)

Bekijk gratis de handleiding van Daikin RYYQ24U7Y1B, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelRYYQ24U7Y1B
CategorieNiet gecategoriseerd
TaalNederlands
Grootte8429 MB