Daikin RXYSA8AMY1B handleiding
Handleiding
Je bekijkt pagina 28 van 56

14 Unit installation
Installation and operation manual
28
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1C – 2024.10
14.2 Opening and closing the unit
14.2.1 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
2× 3×
8 HP 10+12 HP
14.2.2 To close the outdoor unit
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1N•m.
2× 3×
8 HP 10+12 HP
14.3 Mounting the outdoor unit
14.3.1 To provide the installation structure
Prepare four sets of anchor bolts, nuts, and washers (field supply) as
follows:
[mm]
>150
620
8 HP: 350 (345~355)
10+12 HP: 490 (485~495)
4×
M12
a
a Make sure not to cover the drain holes of the bottom
plate of the unit.
INFORMATION
The recommended height of the upper protruding part of
the bolts is 20mm.
20
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with
resin washers (a). If the coating on the fastening area is
stripped off, the metal can rust easily.
a
14.3.2 To install the outdoor unit
4× M12
14.3.3 To provide drainage
NOTICE
If drain holes of the outdoor unit are covered by a mounting
base or by floor surface, raise the unit to provide a free
space of more than 150mm under the outdoor unit.
≥150
mm
Drain holes (dimensions in mm)
Model Bottom view [mm]
RXYSA8
307
858
872
892
916
5490497266
91
151
211
277
286
297
68
498
218
281
a
RXYSA10 +
RXYSA12
102
118
62
59
216
130
21
20
32
52
98
89
a
a Drain holes