14 Unit installation
Installation and operation manual
28
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1C – 2024.10
14.2 Opening and closing the unit
14.2.1 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
8 HP 10+12 HP
14.2.2 To close the outdoor unit
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1N•m.
8 HP 10+12 HP
14.3 Mounting the outdoor unit
14.3.1 To provide the installation structure
Prepare four sets of anchor bolts, nuts, and washers (field supply) as
follows:
[mm]
>150
620
8 HP: 350 (345~355)
10+12 HP: 490 (485~495)
M12
a
a Make sure not to cover the drain holes of the bottom
plate of the unit.
INFORMATION
The recommended height of the upper protruding part of
the bolts is 20mm.
20
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with
resin washers (a). If the coating on the fastening area is
stripped off, the metal can rust easily.
a
14.3.2 To install the outdoor unit
M12
14.3.3 To provide drainage
NOTICE
If drain holes of the outdoor unit are covered by a mounting
base or by floor surface, raise the unit to provide a free
space of more than 150mm under the outdoor unit.
≥150
mm
Drain holes (dimensions in mm)
Model Bottom view [mm]
RXYSA8
307
858
872
892
916
5490497266
91
151
211
277
286
297
68
498
218
281
a
RXYSA10 +
RXYSA12
102
118
62
59
216
130
21
20
32
52
98
89
a
a Drain holes