13 Special requirements for R32 units
Installation and operation manual
25
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1C – 2024.10
Step3 The total indoor capacity connected to a branch pipe port
(or pair of branch pipe ports in case of FXMA200/250) MUST be
equal or less than the capacity limit that is derived from the table.
If NOT, change the installation and repeat all of the above steps.
Possible changes:
Increase the area of smallest room (installed & conditioned)
connected to the same branch pipe port.
Reduce the indoor capacity connected to the same branch pipe
port to equal or below the limit.
Split indoor capacity over two separate branch pipe ports.
Fine tune system with more detailed calculations in VRV Xpress.
Example
VRV system serving three rooms via one SV unit. Room1 (20m²) is
served by one indoor unit (32 class) connected to port A. Room2
(42 m²) is served by two indoor units (2×50 class) connected to
portB (no extension and liquid pipe size up has been done). Room3
(150 m²) is served by one indoor unit (200 class) connected to
portsC and D.
Port A is connected to an indoor unit installed in room 1a, that is
serving a different room (room 1b) than where it is installed. The
smallest room size needs to be considered: 20 m². Use the table
under Step2 to find the maximum capacity class limit of the indoor
unit: 140. The selected indoor unit is 32 →OK.
Port B only serves room2: use the table under Step 2 to find the
maximum capacity class limit of the sum of the indoor units. 42m² is
rounded down to 40m²: 200. The sum of both indoor units is exactly
100 →OK.
PortsC and D are combined and must be considered as one branch
pipe. They only serve room3: Use the table under Step2 to find the
maximum capacity class limit of the indoor unit: 250. The selected
indoor unit is 200 →OK.
50 50200
b
a
Room 1a
20
Room 1b
40
Room 3
150
Room 2
42
D C B A
32
c
c
A~D Branch pipe port A~D
a Outdoor unit
b SV unit
c Indoor branch kit (refnet)
Room Room
32/50/200 Indoor unit capacity