12 About the units and options
Installation and operation manual
18
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1C – 2024.10
WARNING
The unit's center of gravity deviates to the right side
(compressor side). If you lift the unit using a crane and you
do not fix a horizontal rope to the lifting hook as shown, the
unit might drop.
Carry the unit slowly as shown:
±134
kg
8HP
±163
kg
10+12HP
11.2 To remove the accessories from
the outdoor unit
1 Remove the service cover. See "14.2.1 To open the outdoor
unit"[428].
2 Remove the accessories.
8 HP 10+12 HP
a
b
c
d
2× (8 HP)
3× (10+12 HP)
f g h i
e
a General safety precautions
b Outdoor unit installation and operation manual
c Multilingual fluorinated greenhouse gases label
d Installation information leaflet
e Declaration of conformity
f Fluorinated greenhouse gases label
g Gas piping accessory1 (only for 10HP:Ø19.1mm)
h Gas piping accessory2 (8HP:Ø19.1mm;
10+12HP:Ø22.2mm)
i Cable tie (8HP:2×; 10+12HP:3×)
11.3 To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.
The transportation stay for protecting the unit during transport must
be removed. Proceed as shown in the figure and procedure below.
1 Remove the bolt (a) and washers.
2 Remove the transportation stay (b) as shown in the figure
below.
1
2
a
b
a Bolt
b Transportation stay
12 About the units and options
12.1 About the outdoor unit
This installation manual concerns the VRV 5-S, full inverter driven,
heat pump system.
These units are intended for outdoor installation and aimed for air to
air heat pump applications.
Specification
Capacity Heating 25~37.5kW
Cooling 22.4~33.5kW
Ambient design
temperature
Heating –20~21°CDB
–20~15.5°CWB
Cooling –5~52°CDB
12.2 System layout
WARNING
The installation MUST comply with the requirements that
apply to this R32 equipment. For more information, see
"13Special requirements for R32 units"[419].
INFORMATION
The following figure is an example and may NOT
completely match your system layout.
a
c
d
e
g
i
f
e
cc
e
h
i
i i
b
e
j
a Heat pump outdoor unit
b Safety valve unit (SV)