15 Electrical installation
Installation and operation manual
30
RXYQQ8~20U7Y1B
VRV IV Q+ series heat pump
4P546221-1B – 2020.10
14.4.8 Error codes when charging refrigerant
Code Cause Solution
Unusual low pressure on
suction line
Close valve A
immediately. Push BS3 to
reset. Check following
items before retrying
autocharge procedure:
Check if the gas side
stop valve is opened
correctly.
Check if the valve of the
refrigerant cylinder is
opened.
Check if the air inlet and
outlet of the indoor unit
are not obstructed.
Freeze-up prevention
indoor unit
Close valve A
immediately. Push BS3 to
reset. Retry autocharge
procedure.
Indoor unit is out of
temperature range for leak
detection operation
Retry when ambient
conditions are satisfied.
Outdoor unit is out of
temperature range for leak
detection operation
Retry when ambient
conditions are satisfied.
Other
malfunction
code
Close valve A
immediately. Confirm the
malfunction code and take
corresponding action,
"19.1Solving problems
based on error
codes"[438].
14.4.9 Checks after charging refrigerant
Are all stop valves open?
Is the amount of refrigerant, that has been added, recorded on the
refrigerant charge label?
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
14.4.10 To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Quantity of fluorinated greenhouse gases of the total
refrigerant charge expressed as tonnes CO
2
equivalent.
f GWP = Global warming potential
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label.
2 Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.
15 Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
15.1 About electrical compliance
This equipment complies with:
EN/IEC 61000‑3‑11
provided that the system impedance Z
sys
is
less than or equal to Z
max
at the interface point between the user's
supply and the public system.
EN/IEC 61000‑3‑11 = European/International Technical
Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for
equipment with rated current ≤75A.
It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a system impedance Z
sys
less than or equal to Z
max
.
EN/IEC 61000‑3‑12 provided that the short-circuit power S
sc
is
greater than or equal to the minimum S
sc
value at the interface
point between the user's supply and the public system.
EN/IEC 61000‑3‑12 = European/International Technical
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16A and ≤75A per phase.
It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
sc
greater than or equal to the
minimum S
sc
value.
Model Z
max
(Ω) Minimum S
sc
value (kVA)
RXYQQ8 4050
RXYQQ10 5535
RXYQQ12 6038
RXYQQ14 6793
RXYQQ16 7547
RXYQQ18 8805
RXYQQ20 9812
RXYQQ22 11573
RXYQQ24 11597
RXYQQ26 12831
RXYQQ28 13585
RXYQQ30 14843
RXYQQ32 15094