Daikin RXYQQ16U7Y1B handleiding

48 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 13 van 48
8 Troubleshooting
Installation and operation manual
13
RXYQQ8~20U7Y1B
VRV IV Q+ series heat pump
4P546221-1B – 2020.10
If after checking all above items, it is impossible to fix the problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).
8.1 Error codes: Overview
In case a malfunction code appears on the indoor unit user interface
display, contact your installer and inform the malfunction code, the
unit type, and serial number (you can find this information on the
nameplate of the unit).
For your reference, a list with malfunction codes is provided. You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.
Main code Contents
External protection device was activated
EEPROM failure (indoor)
Drain system malfunction (indoor)
Fan motor malfunction (indoor)
Swing flap motor malfunction (indoor)
Expansion valve malfunction (indoor)
Drain malfunction (indoor unit)
Filter dust chamber malfunction (indoor)
Capacity setting malfunction (indoor)
Transmission malfunction between main PCB and sub
PCB (indoor)
Heat exchanger thermistor malfunction (indoor; liquid)
Heat exchanger thermistor malfunction (indoor; gas)
Suction air thermistor malfunction (indoor)
Discharge air thermistor malfunction (indoor)
Movement detector or floor temperature sensor
malfunction (indoor)
User interface thermistor malfunction (indoor)
PCB malfunction (outdoor)
Current leakage detector was activated (outdoor)
High pressure switch was activated
Low pressure malfunction (outdoor)
Compressor lock detection (outdoor)
Fan motor malfunction (outdoor)
Electronic expansion valve malfunction (outdoor)
Discharge temperature malfunction (outdoor)
Abnormal suction temperature (outdoor)
Refrigerant overcharge detection
High pressure switch malfunction
Low pressure switch malfunction
Fan motor trouble (outdoor)
Ambient temperature sensor malfunction (outdoor)
Pressure sensor malfunction
Current sensor malfunction
Discharge temperature sensor malfunction (outdoor)
Heat exchanger gas temperature sensor malfunction
(outdoor)
Suction temperature sensor malfunction (outdoor)
De-icing temperature sensor malfunction (outdoor)
Liquid temperature sensor (after subcool HE)
malfunction (outdoor)
Liquid temperature sensor (coil) malfunction (outdoor)
Gas temperature sensor (after subcool HE)
malfunction (outdoor)
Main code Contents
High pressure sensor malfunction (S1NPH)
Low pressure sensor malfunction (S1NPL)
INV PCB abnormal
Fin temperature abnormal
Inverter PCB faulty
Compressor over current detected
Compressor lock (startup)
Transmission outdoor unit - inverter: INV transmission
trouble
INV unbalanced power supply voltage
Autocharge operation related
Fin thermistor malfunction
Autocharge operation related
Autocharge operation related
Autocharge operation related
Capacity setting malfunction (outdoor)
Abnormal low pressure drop, faulty expansion valve
Reversed power supply phase malfunction
INV voltage power shortage
System test run not yet executed
Faulty wiring indoor/outdoor
Abnormal user interface - indoor communication
Faulty wiring to outdoor/outdoor
Abnormal main-sub user interface communication
System mismatch. Wrong type of indoor units
combined. Indoor unit malfunction.
Connection malfunction over indoor units or type
mismatch
Centralised address duplication
Malfunction in communication centralised control
device - indoor unit
Auto address malfunction (inconsistency)
Auto address malfunction (inconsistency)
8.2 Symptoms that are NOT system
malfunctions
The following symptoms are NOT system malfunctions:
8.2.1 Symptom: The system does not operate
The air conditioner does not start immediately after the ON/OFF
button on the user interface is pressed. If the operation lamp
lights, the system is in normal condition. To prevent overloading of
the compressor motor, the air conditioner starts 5 minutes after it
is turned ON again in case it was turned OFF just before. The
same starting delay occurs after the operation mode selector
button was used.
If "Under Centralized Control" is displayed on the user interface,
pressing the operation button causes the display to blink for a few
seconds. The blinking display indicates that the user interface
cannot be used.
The system does not start immediately after the power supply is
turned on. Wait one minute until the micro computer is prepared
for operation.

Bekijk gratis de handleiding van Daikin RXYQQ16U7Y1B, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelRXYQQ16U7Y1B
CategorieNiet gecategoriseerd
TaalNederlands
Grootte8215 MB