14 Piping installation
Installation and operation manual
17
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543426-1C – 2025.01
14.1.3 To select refrigerant branch kits
Refrigerant refnets
For piping example, refer to "14.1.2To select the piping size"[415].
When using refnet joints at the first branch counted from the
outdoor unit side, choose from the following table in accordance
with the capacity of the outdoor unit (example: refnet joint a).
Outdoor unit capacity type
(HP)
Refrigerant branch kit
8+10 KHRQ22M29T9
12~22 KHRQ22M64T
24~42 KHRQ22M75T
For refnet joints other than the first branch (example refnet joint b),
select the proper branch kit model based on the total capacity
index of all indoor units connected after the refrigerant branch.
Indoor unit capacity index Refrigerant branch kit
<200 KHRQ22M20T
200≤x<290 KHRQ22M29T9
290≤x<640 KHRQ22M64T
≥640 KHRQ22M75T
Concerning refnet headers, choose from the following table in
accordance with the total capacity of all the indoor units connected
below the refnet header.
Indoor unit capacity index Refrigerant branch kit
<200 KHRQ22M29H
200≤x<290
290≤x<640 KHRQ22M64H
(a)
≥640 KHRQ22M75H
(a)
If the pipe size above the refnet header is Ø34.9mm or more,
KHRQ22M75H is required.
INFORMATION
Maximum 8 branches can be connected to a header.
How to choose an outdoor multi connection piping kit. Choose
from the following table in accordance with the number of outdoor
units.
Number of outdoor units Branch kit name
2 BHFQ22P1007
3 BHFQ22P1517
INFORMATION
Reducers or T-joints are field supplied.
NOTICE
Refrigerant branch kits can only be used with R410A.
14.1.4 Multiple outdoor units: Possible layouts
The piping between the outdoor units must be routed level or
slightly upward to avoid the risk of oil retention into the piping.
Pattern 1
a
b
b
a
Pattern 2
b
a
a
b
a
b
b
a
a
a To indoor unit
b Piping between outdoor units
NOT allowed (oil remains in piping)
Allowed
To avoid the risk of oil retention to the outmost outdoor unit,
always connect the stop valve and the piping between outdoor
units as shown in the correct ( ) possibilities of the figure below.
a
b b b
a
b b b
a
b
a
b
a
b
a
a
a
≥200 mm
a To indoor unit
b Oil collects to the outmost outdoor unit when the system
stops
NOT allowed (oil remains in piping)
Allowed
If the piping length between the outdoor units exceeds 2m, create
a rise of 200 mm or more in the gas line within a length of 2m
from the kit.
If Then
≤2m
a
b
≤2 m
>2m
a
≤2 m ≤2 m
≥200 mm
≥200 mm
b
>2 m >2 m
a To indoor unit
b Piping between outdoor units