20 Technical data
Installation and operation manual
36
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543426-1C – 2025.01
Main code Sub code Cause Solution
Master Slave 1 Slave 2
— Too low pressure was noticed during
leak detection operation
Restart leak detection operation.
— Indicates an indoor unit which is not
compatible with leak detection
functionality is installed (e.g., RADX
indoor unit, Hydrobox, …)
Refer to requirements to be able to
execute leak detection operation.
20 Technical data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of the latest technical data is available on the Daikin
Business Portal (authentication required).
20.1 Service space: Outdoor unit
Make sure the space around the unit is adequate for servicing and
the minimum space for air inlet and air outlet is available (refer to the
figure below and choose one of the possibilities).
a
b
a
c
d
a
b
a
e
d
e
c
a
b
a
e
d
f
c
a
b
a
e
b
d
c
a
b
a
e
d
f
c
1
2
3
4
5
Layout A+B+C+D A+B
Possibility 1 Possibility 2
1
a≥10mm
b≥300mm
c≥10mm
d≥500mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
a≥200mm
b≥300mm
2
a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
a≥200mm
b≥300mm
e≥400mm
Layout A+B+C+D A+B
Possibility 1 Possibility 2
3
a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
f≥600 mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
f≥500mm
—
4
a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
5
a≥10mm
b≥500mm
c≥10mm
d≥500mm
e≥20mm
f≥900mm
a≥50mm
b≥500mm
c≥50mm
d≥500mm
e≥100mm
f≥600mm
—
h
1
h
2
1500
500
F
(mm)
d b
ABCD Sides along the installation site with obstacles
F Front side
Suction side
▪ In case of an installation site where sides A+B+C+D have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to the figure above for impact of
wall heights of sides B+D on service space dimensions.
▪ In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.
▪ The installation space required on these drawings are for full load
heating operation without considering possible ice accumulation. If
the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of
ice in between the outdoor units.
INFORMATION
The service space dimensions in above figure are based
on cooling operation at 35°C ambient temperature
(standard conditions).
INFORMATION
Further specifications can be found in the technical
engineering data.