Daikin RXYLQ24T7Y1B handleiding

40 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 23 van 40
14 Piping installation
Installation and operation manual
23
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543426-1C – 2025.01
Pre-charging refrigerant
Step 1
Calculate additional refrigerant charge amount: R (kg)
Refrigerant overcharge happened, recover
refrigerant to reach R=Q
Step 2
Open valves C and B to the liquid line
Execute pre-charging amount: Q (kg)
Step 3a
Close valves C and B
Charging is finished
Fill in the amount on the additional
refrigerant charge label
Go to test run
Step 3b
Close valves C and B
R=Q R>QR<Q
Continued on next page >>
p
<
p
>
R410AN2
C
A B
Charging refrigerant
Step 5
Proceed with manual charge
Step 6
Activate field setting [2-20]=1
Unit will start manual refrigerant charging operation.
Step 7
Open valve A
Charge remaining amount of refrigerant P (kg)
R=Q+P
Step 8
Close valve A
Push BS3 to stop manual charging
Charging is finished
Fill in the amount on the additional refrigerant charge label
Go to test run
Step 4
Connect valve A to the refrigerant charge port (d)
Open all outdoor unit stop valves
R>Q
<< Continuation of previous page
p
<
p
>
R410A
d
A

Bekijk gratis de handleiding van Daikin RXYLQ24T7Y1B, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelRXYLQ24T7Y1B
CategorieNiet gecategoriseerd
TaalNederlands
Grootte6679 MB