8 | Electrical installation
Installer reference guide
48
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
Wire type Installation method
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.5
M4 (earth)
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
8.2.4 Specifications of standard wiring components
Component
Power supply cable Voltage 220~240V
Phase 1~
Frequency 50Hz
Wire sizes MUST comply with applicable
legislation
Interconnection cable (indoor↔outdoor) 4-core cable ≥1.5 mm² and
applicable for 220~240 V
Recommended field fuse 16A
Earth leakage circuit breaker MUST comply with applicable
legislation
8.2.5 To connect the electrical wiring to the outdoor unit
1 Remove the service cover. See "6.2.2To open the outdoor unit"[429].
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Open the wire clamp.