14 | Maintenance and service
Installer reference guide
63
ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B +
RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B
R32 split series
4P513661-9J – 2020.05
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked
heat exchanger can lead to too low pressure or too high pressure leading to
worse performance.
14.4 About the compressor
When servicing the compressor keep in mind following precautions:
DANGER: RISK OF ELECTROCUTION
Use this compressor on a grounded system only.
Turn the power off before servicing the compressor.
Reattach the switch box cover and service lid after servicing.
CAUTION
Always wear safety goggles and protective gloves.
DANGER: RISK OF EXPLOSION
Use a pipe cutter to remove the compressor.
Do NOT use the brazing torch.
Use approved refrigerants and lubricants only.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the compressor with bare hands.