Daikin RXF20A2V1B handleiding

76 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 53 van 76
9 | Electrical installation
Installer reference guide
53
ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B +
RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B
R32 split series
4P513661-9J – 2020.05
Component
Recommended circuit breaker RXM71R
RXP50~71M
RXF50+60B
RXF71A
ARXF50~71A
20A
(a)
ARXM50~71R
RXM50+60R
16A
RXM42R
RXA42+50R
RXJ50N
13A
Earth leakage circuit breaker MUST comply with applicable legislation
(a)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16A and ≤75A per phase).
9.2 To connect the electrical wiring to the outdoor unit
1 Remove the switch box cover.
2
1
1
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Open the wire clamp.
4 Connect the interconnection cable and power supply as follows:
50 Hz
220-240 V
c d
f
a b e
a Interconnection cable
b Power supply cable
c Circuit breaker
d Residual current device
e Power supply

Bekijk gratis de handleiding van Daikin RXF20A2V1B, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelRXF20A2V1B
CategorieNiet gecategoriseerd
TaalNederlands
Grootte10277 MB