9 | Electrical installation
Installer reference guide
50
RXA-A8
R32 Split system air conditioners
4P519439-23X – 2023.09
1-3
9.1.3 Specifications of standard wiring components
Power supply
Voltage 220~240V
Frequency 50Hz
Phase 1~
Current RXA20: 9.88A
RXA25: 11.17A
RXA35: 12.29A
Components
Power supply cable MUST comply with national wiring regulation
3-core cable
Wire size based on the current, but not less than
2.5mm
2
Interconnection cable
(indoor↔outdoor)
Only use harmonised wire providing double
insulation and suitable for applicable voltage
4-core cable
Minimum size 1.5mm
2
Recommended circuit breaker Class 20: 10A
Class 25+35: 13A
Earth leakage circuit breaker /
residual current circuit
breaker
MUST comply with national wiring regulation
9.2 To connect the electrical wiring to the outdoor unit
1 Remove the service cover. See "6.2.2To open the outdoor unit"[429].
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Open the wire clamp.
4 Connect the interconnection cable and power supply as follows: