Daikin RXA25A3V1B handleiding
Handleiding
Je bekijkt pagina 31 van 68

6 | Unit installation
Installer reference guide
31
RXJ-M(9)_RXA-A(9)_RXM-R(9)_ARXM-R(9)
R32 Split system air conditioners
4P519439-12M – 2021.02
311
574
211
(mm)
211
a
a 100mm above expected level of snow
6.3.4 To install the outdoor unit
4× M8/M10
6.3.5 To provide drainage
▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is proper drainage in order to
avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drain waste water
away from the unit.
▪ Avoid drain water flowing over the footpath, so that it does NOT become slippery
in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within 150mm of the
bottom side of the unit in order to prevent water from getting into the unit and
to avoid drain water dripping (see the following figure).