Daikin RXA20A5V1B8 handleiding
Handleiding
Je bekijkt pagina 53 van 72

11 | Configuration
Installer reference guide
53
RXA-A8
R32 Split system air conditioners
4P519439-23X – 2023.09
11 Configuration
11.1 Facility setting
Use this function for cooling at low outdoor temperature. This function is designed
for facilities such as equipment of computer rooms. NEVER use in a residence or
office where people occupy the space.
11.1.1 To set the facility mode
When cutting jumper J6 on the PCB, the operation range will expand to –15°C. The
facility mode will stop if the outdoor temperature drops below –20°C and resume
when the temperature rises again.
To cut jumper J6
1 Remove the top plate of the outdoor unit.
2 Remove the front plate.
3 Remove the drip proof cover.
4 Cut jumper J6 on the outdoor unit PCB.
J12
J11
J9
J8
J6
J5
INFORMATION
▪ The indoor unit may produce Intermittent noise due to the outdoor unit fan
turning ON and/or OFF.
▪ Do NOT place humidifiers or other items which might raise humidity in rooms
when you use the facility mode.
▪ Cutting jumper J6 sets the indoor unit fan to the highest speed.
▪ Do NOT use this setting in residences or offices with people.