6 | Unit installation
Installer reference guide
32
RXA-A8
R32 Split system air conditioners
4P519439-23X – 2023.09
NOTICE
If the unit is installed in a cold climate, take adequate measures so that the
evacuated condensate CANNOT freeze.
NOTICE
If the drain holes of the outdoor unit are blocked up by a mounting base or floor
surface, place additional foot bases ≤30mm under the outdoor unit's feet.
INFORMATION
For information on the available options, contact your dealer.
1 Use a drain plug for drainage.
2 Use a Ø16mm hose (field supply).
b
c
d
a
a Drain port
b Bottom frame
c Drain plug
d Hose (field supply)
6.3.6 To prevent the outdoor unit from falling over
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1 Prepare 2 cables as indicated in the following illustration (field supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit to prevent the
cables from scratching the paint (field supply).
4 Attach the ends of the cables.
5 Tighten the cables.