14 Unit installation
Installation and operation manual
27
REMA5A7Y1B9+REYA8~20A7Y1B9
VRV 5 heat recovery
4P797563-1 – 2024.11
14.2.2 To open the switch box of the outdoor
unit
NOTICE
Do NOT apply excessive force when opening the switch
box cover. Excessive force can deform the cover, resulting
in entering of water to cause equipment failure.
5~12 HP
SW8
14~20 HP
SW8
NOTICE
When closing the switch box cover, make sure that the
sealing material on the lower back side of the cover is NOT
caught and bent towards the inside (see figure below).
a
b
c
d
e
a Switch box cover
b Front side
c Power supply terminal block
d Sealing material
e Moisture and dirt could enter
NOT allowed
Allowed
14.3 Mounting the outdoor unit
14.3.1 To provide the installation structure
Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise.
NOTICE
When the installation height of the unit needs to be
increased, do NOT use stands to only support the
corners.
Stands under the unit must be at least 100mm wide.
NOTICE
The height of the foundation must at least be 150mm from
the floor. In heavy snowfall areas, this height should be
increased up to the average expected snow level,
depending on the installation place and condition.
≥100 mm
≥100 mm
*
NOT allowed
Allowed (* = preferred installation)
The preferred installation is on a solid longitudinal foundation
(steel beam frame or concrete). The foundation must be larger
than the grey marked area.
729
≤613
≥929
AB
AA
a
(mm)
Minimum foundation
a Anchor point (4×)
HP AA AB
5~12 766 992
14~20 1076 1302
Fasten the unit in place using four foundation bolts M12. It is best
to screw in the foundation bolts until their length remains 20mm
above the foundation surface.
20 mm
NOTICE
Prepare a water drainage channel around the
foundation to drain waste water from around the unit.
During heating operation and when the outdoor
temperatures are negative, the drained water from the
outdoor unit will freeze up. If the water drainage is not
taken care of, the area around the unit might be very
slippery.
When installed in a corrosive environment, use a nut
with plastic washer (a) to protect the nut tightening part
from rust.
a
14.3.2 To install the outdoor unit
1 Transport the unit by crane or forklift and put it onto the
installation structure.
2 Fix the unit to the installation structure.
3 If transported by crane, remove the slings.

Bekijk gratis de handleiding van Daikin REYA8A7Y1B9, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.