6 Operation
Installation and operation manual
12
REMA5A7Y1B9+REYA8~20A7Y1B9
VRV 5 heat recovery
4P797563-1 – 2024.11
6.3.2 To use the dry program
To start
1 Press the operation mode selector button on the user interface
several times and select (program dry operation).
2 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system starts
operating.
3 Press the air flow direction adjust button (only for double-flow,
multi-flow, corner, ceiling-suspended and wall-mounted). Refer
to "6.4Adjusting the air flow direction"[412] for details.
To stop
4 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops
operating.
NOTICE
Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.
6.4 Adjusting the air flow direction
Refer to the operation manual of the user interface.
6.4.1 About the air flow flap
Air flow flap types:
▪ Double flow + multi-flow units
▪ Corner units
▪ Ceiling suspended units
▪ Wall-mounted units
For the following conditions, a micro computer controls the air flow
direction which may be different from the display.
Cooling Heating
▪ When the room temperature is
lower than the set
temperature.
▪ When starting operation.
▪ When the room temperature is
higher than the set
temperature.
▪ At defrost operation.
▪ When operating continuously at horizontal air flow direction.
▪ When continuous operation with downward air flow is performed
at the time of cooling with a ceiling-suspended or a wall-mounted
unit, the micro computer may control the flow direction, and then
the user interface indication will also change.
The air flow direction can be adjusted in one of the following ways:
▪ The air flow flap itself adjusts its position.
▪ The air flow direction can be fixed by the user.
▪ Automatic and desired position .
WARNING
NEVER touch the air outlet or the horizontal blades while
the swing flap is in operation. Fingers may become caught
or the unit may break down.
NOTICE
▪ The movable limit of the flap is changeable. Contact
your dealer for details. (only for double-flow, multi-flow,
corner, ceiling-suspended and wall-mounted).
▪ Avoid operating in the horizontal direction . It may
cause dew or dust to settle on the ceiling or flap.
6.5 Setting the master user interface
6.5.1 About setting the master user interface
INFORMATION
The following figure is an example and may NOT
completely match your system layout.
a
b
c c c c
d d d d
b
a Outdoor unit
b BS unit
c VRV DX indoor unit
d User interface
When the system is installed as shown in the figure above, it is
necessary to – for each subsystem – designate one of the user
interfaces as the master user interface.
The displays of slave user interfaces show (changeover under
centralised control) and slave user interfaces automatically follow the
operation mode directed by the master user interface.
Only the master user interface can select heating or cooling mode
(cooling/heating masterhood).
6.5.2 To designate the master user interface
1 Press the operation mode selector button of the current master
user interface for 4 seconds. In case this procedure was not yet
performed, the procedure can be executed on the first user
interface operated.
Result: The display showing (changeover under
centralised control) of all slave user interfaces connected to the
same outdoor unit flashes.
2 Press the operation mode selector button of the controller that
you wish to designate as the master user interface.
Result: Designation is completed. This user interface is
designated as the master user interface and the display
showing (changeover under centralised control) vanishes.
The displays of other user interfaces show (changeover
under centralised control).
Refer to the operation manual of the user interface.