4 About the system
Installation and operation manual
10
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P684060-1C – 2024.10
CAUTION
Do NOT touch the heat exchanger fins.
These fins are sharp and could result
in cutting injuries.
4 About the system
The VRV 5 uses R32 refrigerant which is rated as A2L and is mildly
flammable. For compliance with the requirements for enhanced
tightness refrigerating systems and IEC60335-2-40 the installer must
take extra measures. For more information, see "2.1Instructions for
equipment using R32 refrigerant"[46].
The indoor unit part of this VRV 5 heat recovery system can be used
for heating/cooling applications. The type of indoor unit which can be
used depends on the outdoor unit series.
WARNING
Do NOT modify, disassemble, remove, reinstall or
repair the unit yourself as incorrect dismantling or
installation may cause an electrical shock or fire.
Contact your dealer.
In case of accidental refrigerant leaks, make sure there
are no naked flames. The refrigerant itself is entirely
safe, non-toxic and mildly flammable, but it will
generate toxic gas when it accidentally leaks into a
room where combustible air from fan heaters, gas
cookers, etc. is present. Always have qualified service
personnel confirm that the point of leakage has been
repaired or corrected before resuming operation.
WARNING
The unit is equipped with a refrigerant leak detection
system for safety.
To be effective, the unit MUST be electrically powered at
all times after installation, except for short service periods.
NOTICE
Do NOT use the system for other purposes. In order to
avoid any quality deterioration, do NOT use the unit for
cooling precision instruments, food, plants, animals, or
works of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future
system extensions) is available in technical engineering
data and should be consulted. Contact your installer to
receive more information and professional advice.
4.1 System layout
Your VRV 5 heat recovery series outdoor unit can be one of
following models:
Model Description
REYA8~20 Heat recovery model for single or multi-use
REMA5 Heat recovery model for multi-use only
Depending on the type of outdoor unit which is chosen, some
functionality will or will not exist. It will be indicated throughout this
operation manual when certain features have exclusive model rights
or not.
The complete system can be divided into several sub-systems.
These sub-systems have 100% independence regarding the
selection of cooling and heating operation, and each consists of one
individual branch set of a BS unit, and all indoor units connected
downstream.
INFORMATION
The following figure is an example and may NOT
completely match your system layout.
a
c
d
f
h
e
d
cc
d
g
h h
b
a Heat recovery outdoor unit
b Branch selector (BS)
c VRV direct expansion (DX) indoor unit
d Remote controller in normal mode
e Remote controller in alarm only mode
f Remote controller in supervisor mode (mandatory in
some situations)
g Centralised controller (optional)
h Option PCB (optional)
Refrigerant piping
Interconnection and user interface wiring
5 User interface
CAUTION
NEVER touch the internal parts of the controller.
Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may
happen. For checking and adjusting the internal parts,
contact your dealer.
This operation manual offers a non-exhaustive overview of the main
functions of the system.
Detailed information on required actions to achieve certain functions
can be found in the dedicated installation and operation manual of
the indoor unit.
Refer to the operation manual of the installed user interface.
6 Operation
6.1 Operation range
Use the system in the following temperature and humidity ranges for
safe and effective operation.
Cooling Heating
Outdoor temperature –5~46°CDB –20~20°CDB
–20~15.5°C WB
Indoor temperature 21~32°CDB
14~25°C WB
15~27°CDB
Indoor humidity ≤80%
(a)
(a)
To avoid condensation and water dripping out of the unit. If the
temperature or the humidity is beyond these conditions, safety
devices may be put in action and the air conditioner may not
operate.
Above operation range is only valid in case direct expansion indoor
units are connected to the VRV 5 system.