14 Unit installation
Installation and operation manual
23
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P684060-1C – 2024.10
Check if smallest area of
lowest underground floor
meets the requirements
Start installation
Derive maximum system charge.
See step 3 in above text.
Determine smallest room area
of the lowest underground floor.
Change installation for this port:
1. Increase area of smallest underground
room (installed & conditioned).
OR
2. Decrease piping length by changing layout
OR
3. Add additional countermeasures
as described in applicable legislation.
Total charge amount
<
Total charge limit?
A
min
[m²]
Total charge limit
[kg]
Derive total charge amount.
See step 4 in above text.
Total charge amount
[kg]
YES
NO
Continued from previous column/page
14 Unit installation
WARNING
The installation MUST comply with the requirements that
apply to this R32 equipment. For more information, see
"13Special requirements for R32 units"[417].
14.1 Preparing the installation site
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
WARNING
The appliance shall be stored/installed as follows:
in such a way as to prevent mechanical damage.
in a well-ventilated room without continuously operating
ignition sources (example: open flames, an operating
gas appliance or an operating electric heater).
in a room with dimensions as specified in "13 Special
requirements for R32 units"[417].
14.1.1 Installation site requirements of the
outdoor unit
Mind the spacing guidelines. See the "Technical data" chapter.
INFORMATION
Equipment meets the requirement for commercial and
light-industrial location when professionally installed and
maintained.
INFORMATION
The sound pressure level is less than 70dBA.
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment.
CAUTION
This equipment is NOT intended for use in residential
locations and will NOT guarantee to provide adequate
protection to radio reception in such locations.
NOTICE
If the equipment is installed closer than 30 m to a
residential location, the professional installer MUST
evaluate the EMC situation before installation.
NOTICE
The installation and any maintenance requires a
professional with relevant EMC experience to install any
specific EMC mitigation measures defined in the user