15 Piping installation
Installation and operation manual
25
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P684060-1C – 2024.10
≥100 mm
≥100 mm
*
NOT allowed
Allowed (* = preferred installation)
The preferred installation is on a solid longitudinal foundation
(steel beam frame or concrete). The foundation must be larger
than the grey marked area.
729
≤613
≥929
AB
AA
a
(mm)
Minimum foundation
a Anchor point (4×)
HP AA AB
5~12 766 992
14~20 1076 1302
Fasten the unit in place using four foundation bolts M12. It is best
to screw in the foundation bolts until their length remains 20mm
above the foundation surface.
20 mm
NOTICE
Prepare a water drainage channel around the
foundation to drain waste water from around the unit.
During heating operation and when the outdoor
temperatures are negative, the drained water from the
outdoor unit will freeze up. If the water drainage is not
taken care of, the area around the unit might be very
slippery.
When installed in a corrosive environment, use a nut
with plastic washer (a) to protect the nut tightening part
from rust.
a
14.3.2 To install the outdoor unit
1 Transport the unit by crane or forklift and put it onto the
installation structure.
2 Fix the unit to the installation structure.
3 If transported by crane, remove the slings.
15 Piping installation
CAUTION
See "2 Specific installer safety instructions" [4 4] to make
sure this installation complies with all safety regulations.
15.1 Preparing refrigerant piping
15.1.1 Refrigerant piping requirements
NOTICE
The piping and other pressure-containing parts shall be
suitable for refrigerant. Use phosphoric acid deoxidised
seamless copper for refrigerant piping.
Foreign materials inside pipes (including oils for fabrication) must
be ≤30mg/10m.
15.1.2 Refrigerant piping material
Piping material
Phosphoric acid deoxidised seamless copper
Flare connections
Only use annealed material.
Piping temper grade and thickness
Outer diameter
(Ø)
Temper grade Thickness (t)
(a)
6.4mm (1/4")
9.5mm (3/8")
12.7mm (1/2")
Annealed (O) ≥0.80mm
t
Ø
15.9mm (5/8") Annealed (O) ≥0.99mm
19.1mm (3/4")
22.2mm (7/8")
Half hard (1/2H) ≥0.80mm
28.6mm (11/8") Half hard (1/2H) ≥0.99mm
(a)
Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.
15.1.3 To select the piping size
Determine the proper size using the following tables and reference
figure (only for indication).
B
A
B
c
e
C
C
D
D
d
b
3
a
8
a
9
D D
d
a
3
a
4
a
1
a
2
C
'
DD
C
''
C
b
1
a
5
a
6
D
a
7
DD
b
2
a1~a9 VRVDX indoor units
b1~b3 BS units
c First indoor branch kit (refnet)
d Indoor branch kit (refnet)
e Outdoor multi connection kit
A~D Piping