13 Special requirements for R32 units
Installation and operation manual
22
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P684060-1C – 2024.10
40 20
32
b
a
Room 3
60
m², underground –2
Room 1
40
m², underground –1
Room 2
60
m², ground level
D C B A
63
c
c
A~D Branch pipe port A~D
a Outdoor unit
b BS unit
c Indoor branch kit (refnet)
Room Room
20/32/40/63 Indoor unit capacity
Ground level Ground level
Underground Underground
Flow chart (for EACH BS unit branch pipe port)
Check if smallest room
size meets requirements
Continued on next column/page
Derive maximum indoor capacity
to connect to branch pipe port.
See step 2 in above text.
Determine smallest room area
served by same branch pipe port.
See step 1 in above text.
Change installation for this port:
1. Increase area of smallest room
(installed & conditioned).
OR
2. Reduce connected indoor capacity
below limit
OR
3. Add additional countermeasures
as described in applicable legislation.
OR
4. Split indoor capacity over 2 separate
BS unit ports.
OR
5. Fine tune system with VRV Xpress.
Total indoor capacity index
<
Capacity index limit?
A
min
[m²]
Indoor capacity
class limit
YES
YES
NO
Any indoor units on
lowest underground floor?
NO
Start installation