Daikin REYA12A7Y1B handleiding
Handleiding
Je bekijkt pagina 6 van 60

2 Specific installer safety instructions
Installation and operation manual
6
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P684060-1C – 2024.10
Electrical installation (see "17Electrical installation"[436])
WARNING
Electrical wiring MUST be in accordance with the
instructions from:
▪ This manual. See "17Electrical installation"[436].
▪ The wiring diagram, which is delivered with the unit,
located at the inside of the service cover. For a
translation of its legend, see "24.3 Wiring diagram:
Outdoor unit"[456].
WARNING
The appliance MUST be installed in accordance with
national wiring regulations.
CAUTION
Do NOT push or place redundant cable length into the unit.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shocks.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, extension cords, or
connections from a star system. They can cause
overheating, electrical shocks or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the national wiring
regulation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
The electrical components shall only be replaced with parts
specified by the appliance manufacturer. Replacement with
other parts may result in the ignition of refrigerant in the
event of a leak.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
▪ When connecting the power supply: connect the earth
cable first, before making the current-carrying
connections.
▪ When disconnecting the power supply: disconnect the
current-carrying cables first, before separating the earth
connection.
▪ The length of the conductors between the power supply
stress relief and the terminal block itself MUST be as
such that the current-carrying wires are tautened before
the earth wire is in case the power supply is pulled
loose from the stress relief.
Commissioning (see "19Commissioning"[444])
WARNING
Commissioning MUST be in accordance with the
instructions from this manual. See
"19Commissioning"[444].
CAUTION
Do NOT perform the test operation while working on
the indoor unit(s).
When performing the test operation, NOT ONLY the
outdoor unit, but the connected indoor unit will operate as
well. Working on an indoor unit while performing a test
operation is dangerous.
CAUTION
Do NOT insert fingers, rods or other objects into the air
inlet or outlet. Do NOT remove the fan guard. When the
fan is rotating at high speed, it will cause injury.
Troubleshooting (see "22Troubleshooting"[447])
WARNING
▪ When carrying out an inspection on the switch box of
the unit, ALWAYS make sure that the unit is
disconnected from the mains. Turn off the respective
circuit breaker.
▪ When a safety device was activated, stop the unit and
find out why the safety device was activated before
resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default
setting. If you are unable to find the cause of the
problem, call your dealer.
WARNING
Prevent hazards due to inadvertent resetting of the thermal
cut-out: power to this appliance MUST NOT be supplied
through an external switching device, such as a timer, or
connected to a circuit that is regularly turned ON and OFF
by the utility.
2.1 Instructions for equipment using
R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.