13 Special requirements for R32 units
Installation and operation manual
19
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P684060-1C – 2024.10
NOT OK OK Case
3
e
c
a b
e
c
a
b
In case of one R32 safety system compatible
remote controller, it should be the master and in
the same room of the indoor unit.
4
e
c
a
b
e
c
a
b
e
In case a ducted indoor unit serves a different
room than where it is installed, both supply and
return air MUST be directly ducted to that room.
The room area and remote controller rules MUST
be followed for both installed and served room.
5
e
e
c
a
b
f
e
c
a
b
In case of two R32 safety system compatible
remote controllers, at least one remote controller
should be in the room of the indoor.
6
c c
e
a
b
c c c
e
a
b
Group control is allowed up to a maximum of
10indoor units connected to different ports or
connected to the same port. At least one R32
safety system compatible remote controller should
be in the room of the indoors.
7
c c c
e
a
b
c c c
e
a
b
All indoor units under group control need to be
conditioning the same room.
8
c
e
c
e
f
g
a b
In room: master remote controller in fully functional OR alarm only.
In supervisor room: supervisor remote controller
In particular situations it is mandatory to install a
remote controller at a supervised location
a Outdoor unit
b BS unit
c Indoor unit
d Remote controller NOT compatible with R32 safety
system
e Remote controller compatible with R32 safety system
f Remote controller in supervisor mode
g Supervisor room
13.3 About the charge limit
The charge limit must be determined separately for each BS unit
branch pipe port.
This is possible because of the shut-off valves in the BS unit. The
maximum amount of refrigerant that can escape in case of a leak is
determined by the piping length and indoor heat exchanger size.
This is directly linked to the downstream indoor unit capacity of this
piping section.
In case a leak is detected in an indoor unit, the shut-off valves in the
BS unit of the respective port will close. The piping section with the
leak is now shut off from the rest of the system and the amount of
refrigerant that can leak is significantly reduced.
Note: When two branch pipe ports are combined in order to form a
single branch pipe port (e.g. FXMA200/250), they must be
considered as a single branch pipe port.
13.4 To determine the charge limit
Step 1 In order to derive the total refrigerant charge limit in the
system, determine the area
of the rooms where an indoor unit is installed,
AND of the area of the rooms served by a ducted indoor unit
installed in a different room.