8 Troubleshooting
Installation and operation manual
14
REMA5A7Y1B9+REYA8~20A7Y1B9
VRV 5 heat recovery
4P797563-1 – 2024.11
Malfunction Measure
If the system goes into
fan only operation, but
as soon as it goes into
heating or cooling
operation, the system
stops.
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles.
Remove any obstacles and make sure
the air can flow freely.
▪ Check if the user interface display shows
on the home screen. Refer to the
installation and operation manual
delivered with the indoor unit.
The system operates
but cooling or heating
is insufficient.
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles.
Remove any obstacles and make sure
the air can flow freely.
▪ Check if the air filter is not clogged (refer
to "Maintenance" in the indoor unit
manual).
▪ Check the temperature setting.
▪ Check the fan speed setting on your user
interface.
▪ Check for open doors or windows. Close
doors and windows to prevent wind from
coming in.
▪ Check if there are too many occupants in
the room during cooling operation. Check
if the heat source of the room is
excessive.
▪ Check if direct sunlight enters the room.
Use curtains or blinds.
▪ Check if the air flow angle is proper.
After checking all the items above, if it is impossible to fix the
problem yourself, contact your installer and state the symptoms, the
complete model name of the unit (with manufacturing number if
possible) and the installation date.
8.1 Error codes: Overview
In case a malfunction code appears on the indoor unit user interface
display, contact your installer and inform the malfunction code, the
unit type, and serial number (you can find this information on the
nameplate of the unit).
For your reference, a list with malfunction codes is provided. You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.
Main code Contents
External protection device was activated
The R32 sensor in one of the indoor units has
detected a refrigerant leak
(a)
The R32 sensor in one of the BS unit has detected a
refrigerant leak.
/ Safety system error (leak detection)
(a)
EEPROM failure (indoor)
Drain system malfunction (indoor/BS unit)
Fan motor malfunction (indoor)
Swing flap motor malfunction (indoor)
Expansion valve malfunction (indoor)
Drain malfunction (indoor unit)
Filter dust chamber malfunction (indoor)
Capacity setting malfunction (indoor)
Transmission malfunction between main PCB and sub
PCB (indoor)
Heat exchanger thermistor malfunction (indoor; liquid)
Main code Contents
Heat exchanger thermistor malfunction (indoor; gas)
Suction air thermistor malfunction (indoor)
Discharge air thermistor malfunction (indoor)
Movement detector or floor temperature sensor
malfunction (indoor)
R32 sensor malfunction in one of the indoor units
(a)
R32 sensor end of lifetime in one of the indoor units
(a)
R32 sensor end of lifetime<6months in one of the
indoor units
(a)
Waiting for indoor unit R32 sensor replacement input
(a)
Waiting for BS unit replacement input
BS unit R32 sensor malfunction
Less than 6 months before the BS unit R32 sensor
end of lifetime
BS unit R32 sensor end of lifetime
User interface thermistor malfunction (indoor)
PCB malfunction (outdoor)
Current leakage detector was activated (outdoor)
High pressure switch was activated
Low pressure malfunction (outdoor)
Compressor lock detection (outdoor)
Fan motor malfunction (outdoor)
Electronic expansion valve malfunction (outdoor)
BS unit damper malfunction
Discharge temperature malfunction (outdoor)
Abnormal suction temperature (outdoor)
Refrigerant overcharge detection
High pressure switch malfunction
Low pressure switch malfunction
Fan motor malfunction (outdoor)
Ambient temperature sensor malfunction (outdoor)
Discharge temperature sensor malfunction (outdoor)
Suction temperature sensor malfunction (outdoor)
De-icing temperature sensor malfunction (outdoor) or
heat exchanger gas temperature sensor malfunction
(outdoor)
Liquid temperature sensor (after subcool HE)
malfunction (outdoor)
Liquid temperature sensor (coil) malfunction (outdoor)
Gas temperature sensor (after subcool HE)
malfunction (outdoor)
High pressure sensor malfunction (S1NPH)
Low pressure sensor malfunction (S1NPL)
INV PCB abnormal
Fin temperature abnormal
INV PCB abnormal
Compressor over current detected
Compressor lock (startup)
Transmission outdoor unit - inverter: INV transmission
trouble
INV unbalanced power supply voltage
Fin thermistor malfunction
Capacity setting malfunction (outdoor)
Abnormal low pressure drop, faulty expansion valve
Reversed power supply phase malfunction
INV voltage power shortage