10 About the box
Installation and operation manual
13
LREN8~12A + LRNUN5A
CO ZEAS outdoor unit and capacity up unit
4P704141-1F – 2024.12
a b
a Outdoor unit
b Capacity up unit
Remove the top pallets, top trays and all corner supports. For the
outdoor unit also remove the 2 middle supports.
b
c
a
c
b
c
d
c
c
d
c
b
a
a
a Top pallet
b Top tray
c Corner support
d Middle support (for outdoor unit)
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
consequence: suffocation.
2 The unit is fixed to the pallet with bolts. Remove these bolts.
a b
a Outdoor unit
b Capacity up unit
10.1.3 To handle the outdoor unit
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium
fins of the unit.
1 Unpack the outdoor unit and capacity up unit. See also
"10.1.2To unpack the outdoor unit"[412].
2 Make sure to read the label about handling the unit, located on
the front packaging corner support.
3 There are 2 ways to lift the outdoor unit.
with a crane and 2 belts of at least 8m long as shown in the figure
below. Always use protectors to prevent belt damage and pay
attention to the centre of gravity of the unit.
WARNING
Do NOT use the middle opening of the outdoor unit to
attach the belts.
ALWAYS use the outer openings.
NOTICE
Use a belt sling that adequately bears the weight of the
unit.
Use protection between the casing and the belts.
The width of the holes for belts in the outdoor unit is
70mm.
Outdoor unit
If a forklift is used, pass the forklift arms through the middle and
outer right opening on the bottom of the unit as shown in the figure
below.
WARNING
Do NOT use the outer left opening of the outdoor unit for
lifting the unit with a forklift.
NOTICE
Precautions when lifting the outdoor unit with a forklift
Use filler cloth on the forklift arms to prevent damage to
the unit. Damage to the painting of the unit decreases
the anti-corrosion protection.
In case of damage, remove burrs and paint the edges
and areas around the holes using anti-corrosion
treatment/repair paint to prevent rusting after handling
the unit.
Outdoor unit
4 Lift the capacity up unit with a crane and 2 belts of at least 8m
long as shown in the figure below. Always use protectors to
prevent belt damage and pay attention to the centre of gravity
of the unit.