Handleiding
Je bekijkt pagina 20 van 64

20
Straddle version:
Before mounting the unit prepare the cuts in the cold room wall as shown in the picture.
Fix the unit in place with the appropriate screws. Position the unit on the cold room, connect the evaporator
drain tray spigot and the hole prepared in the cold room wall using the supplied pipe with pre-inserted
heater (for low temperature units only). Fill the hole in the wall with insulating material, polyurethane or
silicone, and mount the hole cover.
Mod. B C D E F G
LMSMD030-050-060-075-100/LMSLN100-120-170 324 295 80 55 147,5 147,5
LMSMD102-120-122-130 / LMSLN172-200 324 595 80 55 297,5 297,5
LMSMD150-200 / LMSLN300 400 542 65 85 271 271
Thru-wall version (optional):
A) Prepare a opening with suitable dimensions in the cold room wall (see picture).
B) Position the unit onto the cold room wall inserting the evaporator section in the opening.
C) Fix the unit using the screws supplied.
ATTENTION
Check that the unit and its devices have suffered no damages during transport. Pay
special attention to the components
secured to the electric panel door and to the refrigerating circuit pipes. Mount the unit
as shown in the drawings; make sure that the electric connections are carried out
properly.
Max 120
Max 120
Inject silicone all around
the panel opening
H
I
Hole
Mod. H I
LMSMD030-050-060-075-100/LMSLN100-120-170 425 335
LMSMD102-120-122-130 / LMSLN172-200 725 335
LMSMD150-200 / LMSLN300 725 475