6.4 Free room
When installing the unit leave enough free room to allow opening, correct use and easy maintenance in safe
conditions.
6.5 Installation
Prepare an opening with suitable dimensions in the cold room wall (see picture).
-Iniettare silicone su tutto il perimetro del tampone.
Sul lato superiore eseguire l’operazione prima del posizionamento.
-Inject silicone all around the panel opening.
Apply silicone on the upper side before positioning the unit.
-Injecter de la silicone sur tout le périmètre du tampon.
Sur la partie supérieure injecter avant de fixer l’Uniblock.
-Silikon auf den ganzen Öffnungsumfang einspritzen.
Bevor der Uniblock eingebaut wird, dieses Verfahren auf der Oberseite ausführen.
-Inyectar silicona sobre todo el perimetro del agujero.
Sobre la parte superior se coloca antes de situar el Uniblock.
425
-Foro
-Hole
-Trou
-Loch
-Agujero
A B C D E F G H I
LMD MF075/LF170 705 300 305 100 420 305 425 100 10
LMD MF100-120/LF200 695 300 305 100 420 305 725 100 10
LMD MF230/LF350 800 470 400 120 580 475 725 100 10
LMD MF350/LF500 857 470 440 120 580 480 1130 100 18
LMD MF400-600/LF600-750 857 500 440 120 850 510 1600 100 22
LMD MF750/LFM000 857 570 490 120 970 580 1640 100 22
A) Position the unit on the cold room inserting the evaporator section in the opening.
B) Fix the unit using the screws supplied.
C) Fit a drain line to the defrost water drain connection in the lower part of the condensing
unit.
N.B.: Before siting the unit (only for the models LMD MF075/LF170), dismount the front panel A.
Inject silicone seal all around
the panel opening
Hole
Condensate drain
line D (I)
A