9 Disposal
Operation manual
26
LMCEY1A/W + LMCEY2A/W
Daikin LMC
4P753996-1 – 2024.06
Display
code
Description Trigger Effect Reset Troubleshooting
Only double circuit units
Display
code
Description Trigger Effect Reset Troubleshooting
Ed2
Defrost on second
evaporator terminated
after maximum time.
Defrost on evaporator
2 ended by defrost
timeout dP2.
Defrost ends, nomral
operation starts.
Defrost ends and
unit continues
operation.
▪ Check if the evaporator is properly
cleaned from ice or dirt.
▪ Avoid to open the cold room door for
a minimum of 4 hours to avoid
moisture and ice, and allow the unit to
perform another defrost.
▪ If the problem persists contact your
dealer/installer.
E7 Th12 discharge circuit
2 prove error.
Th12 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
E8
Th72 discharge circuit
2 prove error.
Th72 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
dA1
Th52 circuit 2 Eva inlet
prove error.
Th52 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
dA2
Th62 circuit 2 Eva
outlet prove error.
Th62 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
EdcB
EVDmin offline. Communication error
between ACU and
EVDmin (dEd = Alarm
at 1440min delay,
product stopped).
Unit stops operation
except the evaporator
fan.
Automatic ▪ Try, if possible, to restart the unit
power.
▪ If the problem persist contact your
dealer/installer.
▪ Check if the unit is working within the
operative temperature range. See
"5.1Operation range"[417].
EE
EEPROM
Malfunctioning.
EEPROM operating
and/or unit parameters
damaged.
Total shutdown. Replace the
driver. Contact
service.
▪ Contact your dealer/installer.
9
Disposal
During normal operation of the unit, no substances arise that need to
be disposed of in a special way.
Wooden, plastic and polystyrene packing must be disposed of
according to the regulations in force in the country where the unit is
used.
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation.
Final disposal of the unit must be done by an authorised
area technical assistance service, that has proper training,
equipment and instructions for the dismantling. They are
also responsible for reuse, recycling and recovery.
▪ Units are marked with the following symbol:
This means that electrical and electronic products may NOT be
mixed with unsorted household waste. Do NOT try to dismantle
the system yourself: dismantling the system, treatment of the
refrigerant, of oil and of other parts MUST be done by an
authorised installer and MUST comply with applicable legislation.
Units MUST be treated at a specialised treatment facility for reuse,
recycling and recovery. By ensuring this product is disposed of
correctly, you will help to prevent potential negative consequences
for the environment and human health. For more information,
contact your installer or local authority.
CAUTION
There are potential environmental hazards involved in
dismantling the unit.
Bekijk gratis de handleiding van Daikin LMCEY, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.