12 Unit installation
Installation and operation manual
17
FXZA15~50A2VEB
VRV system air conditioner
3P599603-1E – 2024.02
c
bba
a Level
b Vinyl tube
c Water level
NOTICE
Do NOT install the unit tilted. Possible consequence: If
the unit is tilted against the direction of the condensate flow
(the drain piping side is raised), the float switch might
malfunction and cause water to drip.
12.2.2 Guidelines when installing the drain
piping
Make sure condensation water can be evacuated properly. This
involves:
General guidelines
Connecting the drain piping to the indoor unit
Checking for water leaks
General guidelines
Pipe length. Keep drain piping as short as possible.
Pipe size. Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 25 mm nominal diameter and
32mm outer diameter).
Slope. Make sure the drain piping slopes down (at least 1/100) to
prevent air from being trapped in the piping. Use hanging bars as
shown.
1~1.5 m
a
a Hanging bar
Allowed
Not allowed
Condensation. Take measures against condensation. Insulate
the complete drain piping in the building.
Rising piping. If necessary to make the slope possible, you can
install rising piping.
Drain hose inclination: 0~75 mm to avoid stress on the piping
and to avoid air bubbles.
Rising piping: ≤300mm from the unit, H2mm perpendicular to
the unit.
H2H1
≤300
≤850
0~75
1000~1500
(mm)
H2
≤645
≤630
H1
205
220
BYFQ60B
BYFQ60C
ba
b c
a
d d
a Metal clamp (accessory)
b Drain hose (accessory)
c Rising drain piping (vinyl pipe of 25mm nominal diameter
and 32mm outer diameter) (field supply)
d Hanging bars (field supply)
Combining drain pipes. You can combine drain pipes. Make
sure to use drain pipes and T-joints with a correct gauge for the
operating capacity of the units.
≥100
H2
(mm)
H2
≤645
≤630
BYFQ60B
BYFQ60C
a
a T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.
1 Push the drain hose as far as possible over the drain pipe
connection.
2 Tighten the metal clamp until the screw head is less than 4mm
from the metal clamp part.
3 Check for water leaks (see "To check for water leaks"[417]).
4 Wind the large sealing pad (= insulation) around the metal
clamp and drain hose, and fix it with tie wraps.
5 Connect the drain piping to the drain hose.
≤4 mm
A
A'
A-A'
A
A'
e
542
c
b
d
b
a
d
c
a
3
1
2~51
a Drain pipe connection (attached to the unit)
b Drain hose (accessory)
c Metal clamp (accessory)
d Large sealing pad (accessory)
e Drain piping (field supply)
To check for water leaks
The procedure differs depending on whether installation of the
system is already completed. When installation of the system is not
yet completed, temporarily connect the user interface and power
supply to the unit.
When installation of the system is not yet completed
1 Temporarily connect electrical wiring.