15 Commissioning
Installation and operation manual
18
FXSN-B
CO VRV system air conditioner
3P672850-3C – 2024.11
15 Commissioning
NOTICE
General commissioning checklist. Next to the
commissioning instructions in this chapter, a general
commissioning checklist is also available on the Daikin
Business Portal (authentication required).
The general commissioning checklist is complementary to
the instructions in this chapter and can be used as a
guideline and reporting template during commissioning and
hand-over to the user.
NOTICE
ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.
15.1 Checklist before commissioning
1 After the installation of the unit, check the items listed below.
2 Close the unit.
3 Power up the unit.
You have read the complete installation and operation
instructions described in the installer and user reference
guide.
Installation
Check that the unit is properly installed, to avoid abnormal
noises and vibrations when starting up the unit.
Drainage
Make sure drainage flows smoothly.
Possible consequence: Condensate water might drip.
Field wiring
Check that the field wiring has been carried out according
to the instructions described in the chapter "14 Electrical
installation" [4 16], according to the wiring diagrams and
according to the applicable national wiring regulation.
Power supply voltage
Check the power supply voltage on the local supply panel.
The voltage MUST correspond to the voltage on the
nameplate of the unit.
Earth wiring
Be sure that the earth wires have been connected
properly and that the earth terminals are tightened.
Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locally
installed protection devices are of the size and type
specified in the chapter "14 Electrical installation" [4 16].
Be sure that no fuse or protection device is bypassed.
Internal wiring
Visually check the switch box and the inside of the unit for
loose connections or damaged electrical components.
Pipe size and pipe insulation
Be sure that correct pipe sizes are installed and that the
insulation work is properly executed.
Damaged equipment
Check the inside of the unit for damaged components or
squeezed pipes.
Field settings
Make sure all field settings you want are set. See
"16.1Field setting"[418].
15.2 To perform a test run
INFORMATION
Perform the test run according to the instructions in the
outdoor unit manual.
The test run is only completed if there is no malfunction
code displayed on the user interface or the outdoor unit
7‑segment display.
See the service manual for the complete list of error
codes and a detailed troubleshooting guideline for each
error.
NOTICE
Do NOT interrupt the test run.
16 Configuration
16.1 Field setting
Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user:
Ceiling height
Bottom suction or rear suction installation
External static pressure setting using:
Airflow automatic adjustment setting
User interface
Air volume when thermostat control is OFF
Time to clean air filter
Thermostat sensor selection
Thermostat differential changeover (if remote sensor is used)
Differential for automatic changeover
Auto-restart after power failure
Setting: Ceiling height
This setting must correspond with the actual distance to the floor,
capacity class and air flow directions.
If the distance to the floor is (m) Then
(1)
M SW
≤2.7 13 (23) 0 01
2.7<x≤3.0 02
3.0<x≤3.5 03
Setting: Bottom suction or rear suction installation
This setting must correspond with the installation type: rear suction
(default) or bottom suction.
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
SW: Setting number
—: Value number
: Default