17 Technical data
Installation and operation manual
20
FXSN-B
CO₂ VRV system air conditioner
3P672850-3C – 2024.11
If you want an interval of…
(air contamination)
Then
(1)
M SW —
±2500h (light) 10 (20) 0 01
±1250h (heavy) 02
Notification ON 3 01
Notification OFF 02
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller
thermostat sensor is used.
When the remote controller thermostat
sensor is…
Then
(1)
M SW —
Used in combination with indoor unit
thermistor
10 (20) 2 01
Not used (indoor unit thermistor only) 02
Used exclusively 03
Setting: Thermostat differential changeover (if remote sensor is
used)
If the system contains a remote sensor, set the increase/decrease
increments.
If you want to change increments to… Then
(1)
M SW —
1°C 12 (22) 2 01
0.5°C 02
Setting: Differential for automatic changeover
Set temperature difference between cooling setpoint and heating
setpoint in automatic mode (availability depends on the system
type). Differential is cooling setpoint minus heating setpoint.
If you want to
set…
Then
(1)
Example
M SW —
0°C 12 (22) 4 01 cooling 24°C/heating
24°C
1°C 02 cooling 24°C/heating
23°C
2°C 03 cooling 24°C/heating
22°C
3°C 04 cooling 24°C/heating
21°C
4°C 05 cooling 24°C/heating
20°C
5°C 06 cooling 24°C/heating
19°C
6°C 07 cooling 24°C/heating
18°C
7°C 08 cooling 24°C/heating
17°C
Setting: Auto-restart after power failure
Depending on the needs of the user, you may disable/enable the
automatic restart after a power failure.
If you want auto-restart after power
failure…
Then
(1)
M SW —
Disabled 12 (22) 5 01
Enabled 02
17 Technical data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of the latest technical data is available on the Daikin
Business Portal (authentication required).
17.1 Wiring diagram
17.1.1 Unified wiring diagram legend
For applied parts and numbering, refer to the wiring diagram on the
unit. Part numbering is by Arabic numbers in ascending order for
each part and is represented in the overview below by "*" in the part
code.
Symbol Meaning Symbol Meaning
Circuit breaker Protective earth
Noiseless earth
Protective earth
(screw)
Connection
A
,
Rectifier
,
Connector Relay connector
Earth Short-circuit
connector
Field wiring Terminal
Fuse Terminal strip
INDOOR
Indoor unit Wire clamp
OUTDOOR
Outdoor unit Heater
Residual current
device
Symbol Colour Symbol Colour
BLK Black ORG Orange
BLU Blue PNK Pink
BRN Brown PRP, PPL Purple
GRN Green RED Red
GRY Grey WHT White
SKY BLU Sky blue YLW Yellow
Symbol Meaning
A*P Printed circuit board
BS* Pushbutton ON/OFF, operation
switch
BZ, H*O Buzzer
C* Capacitor
AC*, CN*, E*, HA*, HE*, HL*,
HN*, HR*, MR*_A, MR*_B, S*, U,
V, W, X*A, K*R_*, NE
Connection, connector
D*, V*D Diode
DB* Diode bridge
DS* DIP switch
E*H Heater
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
• : Default