14 Electrical installation
Installation and operation manual
17
FXSN-B
CO₂ VRV system air conditioner
3P672850-3C – 2024.11
14.2 To connect the electrical wiring to
the indoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ For instructions on how to connect the optional
equipment, see the installation manual delivered with
the optional equipment.
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
It is important to keep the power supply and the interconnection
wiring separated from each other. In order to avoid any electrical
interference, the distance between both wirings should ALWAYS be
at least 50mm.
NOTICE
Be sure to keep the power line and interconnection line
apart from each other. Interconnection wiring and power
supply wiring may cross, but may NOT run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame,
connect the cable to the terminal block (symbols P1, P2) and fix
the cable with a tie wrap.
3 Interconnection cable: Route the cable through the frame,
connect the cable to the terminal block (make sure the symbols
F1, F2 match with the symbols on the outdoor unit), and fix the
cable with a tie wrap.
4 Power supply cable: Route the cable through the frame and
connect the cable to the terminal block (L, N, earth).
10~15
70~90
7
P1P2 F1 F2 T1 T2
c
L N
10~15
70~90
10~20
a
b
a Power supply and earth wiring
b Service cover with wiring diagram
c Interconnection and user interface wiring
5 Fix the cables with a tie wrap.
6 Plastic clamp for tie wrap: Pass tie wraps through the plastic
clamps and fasten to fix the cables.
A
A'
A
A'
A
A'
A
A'
A-A'
a b
c
c
a Small sealing (accessory)
b Wiring
c Plastic clamp for tie wrap
7 Divide the small sealing (accessory) and wrap it around the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.
8 Reattach the service cover.
Complete system example
▪ Example: 1 user interface controls 1 indoor unit.
IN/D OUT/D
F
1 F2 F1 F2
Control box
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
L N L N L N L N
a
d
c
b
NL NL NL NL
a Outdoor unit
b Indoor unit
c User interface
d Most downstream indoor unit
▪ Example: Group control or use with 2 user interfaces.
IN/D OUT/D
F
1 F2 F1 F2
Control box
P
1
P
2
F
1
P
1
P
2
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
P
1
P
2
N
N
L
L
NL L N L N
b
c
e
d
a
a Outdoor unit
b Indoor unit
c User interface (controls 3 indoor units)
d Most downstream indoor unit
e For use with 2 user interfaces
▪ Setting master unit (Cooling/Heating masterhood). In case of
group control, connect the user interface wiring directly to the
master unit. Do not connect user interfaces directly to slave units.
Slave units are restricted in their operation by the master unit (e.g.
1 outdoor unit does not allow for 1 indoor unit to run in cooling
operation while another runs in heating operation). For setting
using the user interface, refer to the manual or reference guide of
the user interface.
▪ 2 or more user interfaces: When using 2 or more user
interfaces, one must be
set to "MAIN" and the other to "SUB". For setting procedure see
the installation
and operation manual of the used user interface.
INFORMATION
In case of group control, it is not necessary to assign a
group address to the indoor unit. The group address is
automatically set when the power is turned on.