12 Unit installation
Installation and operation manual
14
FXSA15~140A2VEB
VRV system air conditioner
3P599602-1C – 2022.02
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment.
▪ Spacing. Mind the following requirements:
≥500
c
A
(mm)
b
a
A Minimum distance to the floor: 2.5m to avoid
accidental touching
a Ceiling
b Floor surface
c Maintenance space
▪ Discharge grille. Minimum requirement installation height of
discharge grille ≥1.8m.
Service space and ceiling opening size
Make sure ceiling opening is big enough to ensure a sufficient
clearance for maintenance and service.
800
800
(mm)
a
b:
≥
500
a
A B
C
≥500
≥
300
A Side view: refrigerant piping, drain piping, control box
B Side view: air inlet
C Top view
a Ceiling opening
Class 15~32: 550mm
Class 40~50: 700mm
Class 63~80: 1000mm
Class 100~125: 1400mm
Class 140: 1550mm
b Service space
Installation options
b
≥1100
A
c
c
d
f
g
125
b ≥800
160
(160~300)
245
h
B
f
g
a
a
e 200
(mm)
h
A Installation with rear canvas duct and duct service
opening
B Installation with bottom canvas duct and air inlet grill
a Ceiling surface
b Ceiling opening
c Air filter
d Air inlet duct
e Duct service opening
f Interchangeable plate
g Canvas connection for air inlet panel (field supply)
h Minimum opening for protective guard (filed supply)
Class 15~32: 504×210mm
Class 40~50: 654×210mm
Class 63~80: 954×210mm
Class 100~125: 1354×210mm
Class 140: 1504×210mm
INFORMATION
Some options may require additional service space. Refer
to the installation manual of the used option before
installation.
12.2 Mounting the indoor unit
12.2.1 Guidelines when installing the indoor unit
INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
Installation options
INFORMATION
The unit can be used with bottom suction by replacing the
interchangeable plate by the air filter holding plate.