16 Configuration
Installation and operation manual
22
FXSA15~140A2VEB
VRV system air conditioner
3P599602-1C – 2022.02
If you want… Then
(1)
M SW
During thermostat
OFF at heating
operation
LL
(2)
12 (22) 3 01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
(a)
Only use in combination with optional remote sensor or when
setting M 10 (20), SW 2, — 03 is used.
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which "Time to clean filter" notification
is displayed on the user interface.
If you want an interval of…
(air contamination)
Then
(1)
M SW
±2500h (light) 10 (20) 0 01
±1250h (heavy) 02
Notification ON 3 01
Notification OFF 02
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller
thermostat sensor is used.
When the remote controller thermostat
sensor is…
Then
(1)
M SW
Used in combination with indoor unit
thermistor
10 (20) 2 01
Not used (indoor unit thermistor only) 02
Used exclusively 03
Setting: Thermostat differential changeover (if remote sensor is
used)
If the system contains a remote sensor, set the increase/decrease
increments.
If you want to change increments to… Then
(1)
M SW
1°C 12 (22) 2 01
0.5°C 02
Setting: Differential for automatic changeover
Set temperature difference between cooling setpoint and heating
setpoint in automatic mode (availability depends on the system
type). Differential is cooling setpoint minus heating setpoint.
If you want to
set…
Then
(1)
Example
M SW
0°C 12 (22) 4 01 cooling 24°C/heating
24°C
1°C 02 cooling 24°C/heating
23°C
2°C 03 cooling 24°C/heating
22°C
3°C 04 cooling 24°C/heating
21°C
4°C 05 cooling 24°C/heating
20°C
5°C 06 cooling 24°C/heating
19°C
6°C 07 cooling 24°C/heating
18°C
7°C 08 cooling 24°C/heating
17°C
Setting: Auto-restart after power failure
Depending on the needs of the user, you may disable/enable the
automatic restart after a power failure.
If you want auto-restart after power
failure…
Then
(1)
M SW
Disabled 12 (22) 5 01
Enabled 02
Setting: T1/T2 input setting
WARNING
In case of R32 refrigerant, terminal connections T1/T2 are
for fire alarm input ONLY. Fire alarm has a higher priority
than R32 safety and shuts the entire system down.
T1
T2
X1M
a
a Fire alarm input signal (potential free contact)
Remote control is available by transmission the external input to the
terminals T1 and T2 on the terminal block for the user interface and
the transmission wiring.
F2 T1
OFF
FORCED
T2
Input A
b
a
a Forced OFF
b Input A
Wiring requirements
Wiring specification Sheathed vinyl cord or 2-core
cable
Wiring size 0.75~1.25 mm
2
Wiring length Maximum 100 m
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
SW: Setting number
—: Value number
: Default
(2)
Fan speed:
LL: Low fan speed (set during thermostat OFF)
L: Low fan speed (set by the user interface)
Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
Monitoring 1, 2: The fan is OFF, but runs for a short time every 6minutes to detect the room temperature by LL (Monitoring 1) or by L
(Monitoring 2).