20 | Configuration
Installer and user reference guide
77
FXNA-A
VRV system air conditioner
4P785124-1 – 2024.09
F2 T1
OFF
FORCED
T2
Input A
b
a
a Forced OFF
b Input A
Wiring requirements
Wiring specification Sheathed vinyl cord or 2-core cable
Wiring size 0.75~1.25 mm
2
Wiring length Maximum 100 m
External contact specification Contact that can make and break the
min. load of DC15 V · 1 mA
This setting must correspond with the needs of the user.
If you want to set… Then
(1)
M SW —
Forced OFF 12 (22) 1 01
ON/OFF Operation 02
Emergency (recommended for alarm operation) 03
Forced OFF - multi tenant 04
Interlocking setting A 05
Interlocking setting B 06
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
• : Default