16 | Unit installation
Installer and user reference guide
48
FXNA-A
VRV system air conditioner
4P785124-1 – 2024.09
16 Unit installation
In this chapter
16.1 Preparing the installation site ................................................................................................................................................ 48
16.1.1 Installation site requirements of the indoor unit.................................................................................................. 48
16.2 Mounting the indoor unit....................................................................................................................................................... 50
16.2.1 Guidelines when installing the indoor unit............................................................................................................ 50
16.2.2 Guidelines when installing the ducting ................................................................................................................. 55
16.2.3 Guidelines when installing the drain piping .......................................................................................................... 56
16.1 Preparing the installation site
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
Choose an installation location with sufficient space to transport the unit in and
out of the site.
Avoid installation in an environment with a lot of organic solvents such as ink and
siloxane.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
16.1.1 Installation site requirements of the indoor unit
Minimum floor area requirements
CAUTION
The total refrigerant charge and/or releasable charge m
rl
in the system cannot
exceed the requirements for minimum floor area of the smallest room that is served.
For minimum floor area requirements for indoor units, go to https://www.daikin.eu
and search for the latest version of the installation and operation manual of the
connected outdoor unit.
INFORMATION
The sound pressure level is less than 70dBA.
WARNING
Keep any required ventilation openings clear of obstructions.
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.