3 | Specific installer safety instructions
Installer and user reference guide
16
FXNA-A
VRV system air conditioner
4P785124-1 – 2024.09
WARNING
▪ Take precautions to avoid excessive vibration or pulsation to refrigeration piping.
▪ Protect the protection devices, piping and fittings as much as possible against
adverse environmental effects.
▪ Provide space for expansion and contraction of long runs of piping.
▪ Design and install piping in refrigerating systems such as to minimise the
likelihood of hydraulic shock damaging the system.
▪ Mount the indoor equipment and pipes securely and protect them to avoid
accidental rupture of equipment or pipes in case of events such as moving
furniture or reconstruction activities.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
▪ there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the
minimum floor area A (m²).
▪ no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching device);
▪ only auxiliary devices approved by the manufacturer are used in the duct work;
▪ air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant
leaks.
NOTICE
▪ Do NOT re-use joints and copper gaskets which have been used already.
▪ Joints made in the installation between parts of the refrigerant system shall be
accessible for maintenance purposes.
CAUTION
Field-made refrigerant joints indoors shall be tightness tested. The test method shall
have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at
least 0,25 times the maximum allowable pressure. No leak shall be detected.