Daikin FXNA32A2VEB handleiding
Handleiding
Je bekijkt pagina 14 van 88

3 | Specific installer safety instructions
Installer and user reference guide
14
FXNA-A
VRV system air conditioner
4P785124-1 – 2024.09
Refrigerant piping installation (see
"17Piping installation"[
4
59]
)
CAUTION
Piping MUST be installed according to instructions given in "17 Piping
installation" [4 59]. Only mechanical joints (e.g. braze+flare connections) that are
compliant with the latest version of ISO14903 can be used.
CAUTION
▪ When mechanical connectors are re-used indoors, renew the sealing parts.
▪ When flared joints are re-used indoors, re-make the flared part.
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
Electrical installation (see
"18Electrical installation"[
4
65]
)
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
▪ All wiring MUST be performed by an authorised electrician and MUST comply
with the national wiring regulation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
▪ If the power supply has a missing or wrong N-phase, equipment might break
down.
▪ Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shocks.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, extension cords, or connections from a star system.
They can cause overheating, electrical shocks or fire.
▪ Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
category III condition, MUST be installed in the fixed wiring.
Bekijk gratis de handleiding van Daikin FXNA32A2VEB, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Daikin |
| Model | FXNA32A2VEB |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 10681 MB |







