14 Electrical installation
Installation and operation manual
20
FXMA-A
VRV system air conditioner
3P680922-1C – 2023.02
Power supply
MCA
(a)
FXMA50: 1.8A
FXMA63: 2A
FXMA80: 2.4A
FXMA100: 3A
FXMA125: 3.2A
(a)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of indoor unit for exact values).
Components
Power supply cable MUST comply with national wiring
regulation.
3-core cable
Wire size based on the current, but not
less than 1.5mm
2
Interconnection wiring
(indoor ↔ outdoor)
Only use harmonised wire providing
double insulation and suitable for
applicable voltage
2-core cable
Minimum size 0.75mm
2
User interface cable Only use harmonised wire providing
double insulation and suitable for
applicable voltage
2-core cable
Minimum size 0.75mm
2
Maximum length 500m
Recommended circuit
breaker
6A
Residual current device MUST comply with national wiring
regulation
14.2 To connect the electrical wiring to
the indoor unit
NOTICE
Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
For instructions on how to connect the optional
equipment, see the installation manual delivered with
the optional equipment.
Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
It is important to keep the power supply and the transmission wiring
separated from each other. In order to avoid any electrical
interference the distance between both wirings should ALWAYS be
at least 50mm.
NOTICE
Be sure to keep the power line and transmission line apart
from each other. Transmission wiring and power supply
wiring may cross, but may NOT run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame,
connect the cable to the terminal block (symbols P1, P2).
3 Interconnection cable: Route the cable through the frame,
connect the cable to the terminal block (make sure the symbols
F1, F2 match with the symbols on the outdoor unit). Bundle the
interconnection cable with the user interface cable and fix them
with a tie wrap on the wiring fixture.
4 Power supply cable: Route the cable through the frame and
connect the cable to the terminal block (L, N, earth). Fix the
cable with a tie wrap on the wiring fixture.
a
b
a Circuit breaker
b Residual current device
10~15
70~90
7
P1P2 F1 F2
b
L N
10~15
70~90
10~20
ca
a Power supply cable
b Service cover with wiring diagram
c User interface cable and interconnection cable
5 Plastic clamp for tie wrap: Pass tie wraps through the plastic
clamps and fasten to fix the cables.
6 Reattach the service cover.
Complete system example
1 user interface controls 1 indoor unit.
LN LN LN
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
N L
d
c
b
LN
N L N L N L
TO OUT/D
TO IN/D
a
a Outdoor unit
b Indoor unit
c User interface
d Most downstream indoor unit
NOTICE
For the use of group control and related limitations refer to
manual of outdoor unit.