Daikin FXKA63AMVEB handleiding

24 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 22 van 24
17 Technical data
Installation and operation manual
22
FXKA-A
VRV system air conditioner
3P747532-2A – 2023.11
F2 T1
OFF
FORCED
T2
Input A
b
a
a Forced OFF
b Input A
Wiring requirements
Wiring specification Sheathed vinyl cord or 2-core
cable
Wiring size 0.75~1.25 mm
2
Wiring length Maximum 100 m
External contact specification Contact that can make and break
the min. load of DC15 V · 1 mA
This setting must correspond with the needs of the user.
If you want to set… Then
(1)
M SW
Forced OFF 12 (22) 1 01
ON/OFF Operation 02
Emergency (recommended for alarm
operation)
03
Forced OFF - multi tenant 04
Interlocking setting A 05
Interlocking setting B 06
Setting: Mold proof prevention operation
NOTICE
When the function is disabled, mould and odour may form
inside the indoor unit.
This setting must correspond with the needs of the user. It
determines the fan operation time after the unit is turned off by the
user interface during cooling mode.
If you want to set the fan operation
time after the unit is turned off to...
Then
(1)
M SW
Disabled 14 (24) 10 01
30minutes 02
60minutes 03
17 Technical data
A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
The full set of the latest technical data is available on the Daikin
Business Portal (authentication required).
17.1 Wiring diagram
17.1.1 Unified wiring diagram legend
For applied parts and numbering, refer to the wiring diagram on the
unit. Part numbering is by Arabic numbers in ascending order for
each part and is represented in the overview below by "*" in the part
code.
Symbol Meaning Symbol Meaning
Circuit breaker Protective earth
Connection Protective earth
(screw)
,
Connector
A
,
Rectifier
Earth Relay connector
Field wiring Short-circuit
connector
Fuse Terminal
INDOOR
Indoor unit Terminal strip
OUTDOOR
Outdoor unit Wire clamp
Residual current
device
Heater
Symbol Colour Symbol Colour
BLK Black ORG Orange
BLU Blue PNK Pink
BRN Brown PRP, PPL Purple
GRN Green RED Red
GRY Grey WHT White
SKY BLU Sky blue YLW Yellow
Symbol Meaning
A*P Printed circuit board
BS* Pushbutton ON/OFF, operation
switch
BZ, H*O Buzzer
C* Capacitor
AC*, CN*, E*, HA*, HE*, HL*,
HN*, HR*, MR*_A, MR*_B, S*, U,
V, W, X*A, K*R_*, NE
Connection, connector
D*, V*D Diode
DB* Diode bridge
DS* DIP switch
E*H Heater
FU*, F*U, (for characteristics,
refer to PCB inside your unit)
Fuse
FG* Connector (frame ground)
H* Harness
H*P, LED*, V*L Pilot lamp, light emitting diode
HAP Light emitting diode (service
monitor green)
HIGH VOLTAGE High voltage
IES Intelligent eye sensor
IPM* Intelligent power module
K*R, KCR, KFR, KHuR, K*M Magnetic relay
L Live
L* Coil
L*R Reactor
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
SW: Setting number
—: Value number
: Default

Bekijk gratis de handleiding van Daikin FXKA63AMVEB, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelFXKA63AMVEB
CategorieAirco
TaalNederlands
Grootte3845 MB