Handleiding
Je bekijkt pagina 6 van 24

3 User safety instructions
Installation and operation manual
6
FXKA-A
VRV system air conditioner
3P747532-2A – 2023.11
2.1 Instructions for equipment using
R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating ignition sources (example: open flames, an
operating gas appliance or an operating electric heater)
and have a room size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation (for example national gas regulation) and are
executed ONLY by authorised persons.
WARNING
▪ Take precautions to avoid excessive vibration or
pulsation to refrigeration piping.
▪ Protect the protection devices, piping and fittings as
much as possible against adverse environmental
effects.
▪ Provide space for expansion and contraction of long
runs of piping.
▪ Design and install piping in refrigerating systems such
as to minimise the likelihood of hydraulic shock
damaging the system.
▪ Mount the indoor equipment and pipes securely and
protect them to avoid accidental rupture of equipment
or pipes in case of events such as moving furniture or
reconstruction activities.
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
CAUTION
Do NOT use potential sources of ignition in searching for
or detection of refrigerant leaks.
NOTICE
▪ Do NOT re-use joints and copper gaskets which have
been used already.
▪ Joints made in the installation between parts of the
refrigerant system shall be accessible for maintenance
purposes.
CAUTION
Field-made refrigerant joints indoors shall be tightness
tested. The test method shall have a sensitivity of 5 grams
per year of refrigerant or better under a pressure of at least
0,25 times the maximum allowable pressure. No leak shall
be detected.
2.1.1 Installation space requirements
CAUTION
The total refrigerant charge and/or releasable charge m
rl
in
the system cannot exceed the requirements for minimum
floor area of the smallest room that is served. For minimum
floor area requirements for indoor units, see the installation
and operation manual of the outdoor unit.
NOTICE
▪ The pipework shall be securely mounted and guarded
protected from physical damage.
▪ Keep the pipework installation to a minimum.
For the user
3 User safety instructions
Always observe the following safety instructions and regulations.
3.1 General
WARNING
If you are NOT sure how to operate the
unit, contact your installer.
WARNING
This appliance can be used by children
aged from 8 years and above and
persons with reduced physical, sensory
or mental capabilities or lack of
experience and knowledge if they have
been given supervision or instruction
concerning use of the appliance in a
safe way and understand the hazards
involved.
Children SHALL NOT play with the
appliance.
Cleaning and user maintenance
SHALL NOT be made by children
without supervision.