7 Maintenance and service
Installation and operation manual
12
FXKA-A
VRV system air conditioner
3P747532-2A – 2023.11
NOTICE
When cleaning the heat exchanger, make sure to remove
the electronic components above it. Water or detergent
might deteriorate the insulation of electronic components
and result in burnout of these components.
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10 minutes,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing. The
voltage MUST be less than 50VDC before you can touch
electrical components. For the location of the terminals,
see the warning label for persons performing service and
maintenance.
A1P
C-
C+
a
A1P Main printed circuit board
a Multimeter
C Residual voltage measuring points
7.2 Cleaning the unit exterior and air
filter
CAUTION
Turn off the unit before cleaning the unit exterior and air
filter.
NOTICE
Do NOT use gasoline, benzene, thinner polishing
powder or liquid insecticide. Possible consequence:
Discoloration and deformation.
Do NOT use water or air of 50°C or higher. Possible
consequence: Discoloration and deformation.
Do NOT scrub firmly when washing the blade with
water. Possible consequence: The surface sealing
peels off.
7.2.1 To clean the exterior
WARNING
Do NOT let the indoor unit get wet. Possible
consequence: Electrical shock or fire.
Clean with a soft cloth. If it is difficult to remove stains, use water or
neutral detergent and wipe with a dry cloth.
7.2.2 To clean the air filter
When to clean the air filter:
Rule of thumb: Clean every 6 months. If the air in the room is
extremely contaminated, increase the cleaning frequency.
Depending on the settings, the user interface can display the
"Time to clean filter" notification. Clean the air filter when the
notification is displayed.
If the dirt becomes impossible to clean, change the air filter
(=optional equipment).
How to clean the air filter:
1 Open the panel. Simultaneously slide the two knobs and open
the decoration panel carefully.
2 Remove the air filters. Holding the filter knob unhook the filter
from the unit (2 places on each filter) and remove the filter.
3 Clean the air filters. Use a vacuum cleaner or wash with water.
If the air filter is very dirty, use a soft brush and neutral
detergent.
4 Dry the air filters in the shadow.
5 Reattach the air filters and close panel.
6 Turn ON the power.
7 To remove warning screens, see the reference guide of the
user interface.
7.3 About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
Periodical inspections for refrigerant leaks may be required
depending on the applicable legislation. Contact your installer for
more information.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
The refrigerant inside the unit is mildly flammable, but
normally does NOT leak. If the refrigerant leaks in the
room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the
formation of a harmful gas.
Turn OFF any combustible heating devices, ventilate
the room, and contact the dealer where you purchased
the unit.
Do NOT use the unit until a service person confirms
that the part from which the refrigerant leaked has been
repaired.