Handleiding
Je bekijkt pagina 9 van 24

7 Maintenance and service
Installation and operation manual
9
FXFN-B
CO₂ VRV system air conditioner
3P672850-2C – 2024.11
Automatic airflow control
Cooling Heating
▪ When the room temperature is
lower than the controller's
setpoint for cooling operation
(including auto operation).
▪ When the indoor units run in
Continuous operation, and the
airflow direction is downward.
▪ When starting operation.
▪ When the room temperature is
higher than the controller's
setpoint for heating operation
(including auto operation).
▪ At defrost operation.
▪ When the indoor units run continuously for a long time and the
airflow direction is Horizontal.
WARNING
NEVER touch the air outlet or the horizontal blades while
the swing flap is in operation. Fingers may become caught
or the unit may break down.
NOTICE
Avoid operating in the horizontal direction. It may cause
dew or dust to settle on the ceiling or flap.
6.2.4 Active circulation airflow
Use active circulation airflow to heat or cool the room more quickly.
INFORMATION
For setting procedure of the active circulation airflow, see
the reference guide or the manual of the used user
interface.
6.3 To operate the system
INFORMATION
For setting of the operation mode, airflow direction, active
circulation airflow or other settings, see the reference guide
or operation manual of the user interface.
7 Maintenance and service
7.1 Precautions for maintenance and
service
CAUTION
See "3 User safety instructions" [4 5] to acknowledge all
related safety instructions.
NOTICE
NEVER inspect or service the unit by yourself. Ask a
qualified service person to perform this work. However, as
end user, you may clean the air filter, suction grille, air
outlet and outside panels.
NOTICE
Maintenance MUST be done by an authorised installer or
service agent.
We recommend performing maintenance at least once a
year. However, applicable legislation might require shorter
maintenance intervals.
NOTICE
Do NOT wipe the controller operation panel with benzine,
thinner, chemical dust cloth, etc. The panel may get
discoloured or the coating peeled off. If it is heavily dirty,
soak a cloth in water-diluted neutral detergent, squeeze it
well and wipe the panel clean. Wipe it with another dry
cloth.
NOTICE
When cleaning the heat exchanger, make sure to remove
the electronic components above it. Water or detergent
might deteriorate the insulation of electronic components
and result in burnout of these components.
Following symbols may occur on the indoor unit:
Symbol Explanation
Measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10 minutes,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing. The
voltage MUST be less than 50VDC before you can touch
electrical components. For the location of the terminals,
see the warning label for persons performing service and
maintenance.
A1P
C-
C+
a
A1P Main printed circuit board
a Multimeter
C Residual voltage measuring points
7.2 Cleaning the air filter, suction
grille, air outlet and outside panels
CAUTION
Turn off the unit before cleaning the air filter, suction grille,
air outlet and outside panels.
NOTICE
▪ Do NOT use gasoline, benzene, thinner polishing
powder or liquid insecticide. Possible consequence:
Discoloration and deformation.
▪ Do NOT use water or air of 50°C or higher. Possible
consequence: Discoloration and deformation.
▪ Do NOT scrub firmly when washing the blade with
water. Possible consequence: The surface sealing
peels off.
7.2.1 To clean the air filter
When to clean the air filter:
▪ Rule of thumb: Clean every 6 months. If the air in the room is
extremely contaminated, increase the cleaning frequency.
▪ Depending on the settings, the user interface can display the
"Time to clean filter" notification. Clean the air filter when the
notification is displayed.
▪ If the dirt becomes impossible to clean, change the air filter
(=optional equipment).