12 Unit installation
Installation and operation manual
15
FXFN-B
CO VRV system air conditioner
3P672850-2C – 2024.11
≥100
≤675
(mm)
a
a T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.
1 Push the drain hose as far as possible over the drain pipe
connection.
2 Tighten the metal clamp until the screw head is less than 4mm
from the metal clamp part.
3 Check for water leaks (see "To check for water leaks"[415]).
4 Install the insulation piece (drain pipe).
5 Wind the large sealing pad (= insulation) around the metal
clamp and drain hose, and fix it with tie wraps.
6 Connect the drain piping to the drain hose.
≤4 mm
A
A'
A-A'
A
A'
f
652
ce
4
ba
d
b
a
d
c
3
1
2~61
a Drain pipe connection (attached to the unit)
b Drain hose (accessory)
c Metal clamp (accessory)
d Large sealing pad (accessory)
e Insulation piece (drain pipe) (accessory)
f Drain piping (field supply)
To check for water leaks
The procedure differs depending on whether installation of the
system is already completed. When installation of the system is not
yet completed, temporarily connect the user interface and power
supply to the unit.
When installation of the system is not yet completed
1 Temporarily connect electrical wiring.
Remove the service cover.
Connect the user interface.
Connect the power supply.
Reattach the service cover.
b
a
c
N L
a Service cover with wiring diagram
b User interface terminal block
c Power supply terminal block
2 Turn ON the power.
3 Start fan only operation (see the reference guide or the service
manual of the user interface).
4 Gradually pour approximately 1 l of water through the air
discharge outlet, and check for leaks.
≥100 mm
e
d
c
b
a
a Plastic watering can
b Service drain outlet (with rubber plug). Use this outlet to
drain water from the drain pan
c Drain pump location
d Drain pipe connection
e Drain pipe
5 Turn OFF the power.
6 Disconnect the electrical wiring.
Remove the service cover.
Disconnect the power supply.
Disconnect the user interface.
Reattach the service cover.
When installation of the system is already completed
1 Start cooling operation (see the reference guide or the service
manual of the user interface).
2 Gradually pour approximately 1 l of water through the water
inlet, and check for leaks (see "When installation of the system
is not yet completed"[415]).